    IGP-EMERGENCY POWER GENERATORS

Emergency power plant 2 x 660kVA parallel:

Consisting of two gensets in parallel operation - 1320kVA - total power output. Available 10sec after starting command.

Consisting of two diesel-engines M.A.N D 2840 LE 213: V10 diesel-engine, 4-stroke, liquid-cooled, direct injection, turbocharged, intercooled, capacity 18,27l.

And two brushless three-phase synchronous generators:
Type Marelli MJB 355 MB4 Nominal output 700kVA


igp

Länge = 3,4m
Breite = 1,25m
Höhe = 1,9m
Gewicht = 4,5t
 
NOx........below 2500 mg/Nm3
CO..........below 250 mg/Nm3
Dust.....below 50 mg/Nm3

Switchboard for emergency-power operation, fully automatic parallel operation with mains for test run and Profibus DB – connection.

Fuel supply: designed for 20h of continuous operation at nominal load, consisting of 6 x 1000l double-walled tanks, connected in parallel with leakage-monitoring, mechanical and electrical level-indicator and minimum-monitoring.

Supply- and exhaust-air sound-insulation: sound level max. 55 dB(A)...7m

Location: gas-tank Haidach, client www.rohoel.at.

   